Introduced the RA-1000 series remote multiplex annunciator of MGC, including its structure, installation, wiring, DIP switch settings and specifications.
This manual provides installation and wiring instructions for MGC's RA-1000 Series Remote Multiplex Annunciator Panels. It covers mechanical mounting for indoor and outdoor enclosures, RS-485 and 24V DC wiring requirements, and DIP switch settings for different fire alarm control panels. The document includes specifications for various annunciator chassis models and their compatibility with specific control panels.
The RA-1000 Series includes main and adder chassis models with different circuit capacities, designed to work with MGC’s Analog and Network Fire Alarm Control Panels. Wiring must follow point-to-point configurations, and DIP switches must be set according to the connected control panel type.
| RS-485 Wiring | Twisted shielded pair; 22 AWG up to 2000 ft, 20 AWG up to 4000 ft |
|---|---|
| 24V DC Power Wiring | Point-to-point configuration; no star wiring or T-tapping allowed |
RS-485 wiring should be twisted shielded pair; use 22 AWG for up to 2000 ft or 20 AWG for up to 4000 ft.
It can be expanded to a maximum of 208 circuit display points.
The wire gauge may be 22 AWG.