This document mainly introduces the University of Pennsylvania fire alarm system design guide
This document serves as a design guide for fire alarm systems at the University of Pennsylvania, revised in February 2023. It outlines general configuration, layout, installation, and testing requirements, mandating adherence to National and Local Codes such as the NEC and NFPA 72. The guide specifies that all components must be UL listed or FM approved and bear the UL label, with a strict preference for Gamewell-FCI standard products.
| Battery Standby Duration | 24 hours |
|---|---|
| Battery Alarm Duration | 10 minutes |
| Spare Battery Capacity | 20 percent |
| Battery Charge Time | 48 hours |
| Audible/Visual Circuit Loading | 60 percent |
| Addressable Circuit Loading | 75 percent |
Manufacturer system components shall be the standard products of Gamewell-FCI, and alternates will not be accepted.
The fire alarm control panel shall be Gamewell-FCI E3 Series or newer version.
The battery must operate the system for 24 hours in standby mode plus 10 minutes in alarm mode, with an additional 20 percent spare capacity.