This manual is for the installation of the SHR 8005R and SHR 14105R light commercial HRV. The system is primarily used for high humidity applications in swimming pools and spas.
This manual provides installation instructions for the Fantech SHR 8005R, a light commercial heat recovery ventilator designed for high humidity environments such as indoor pools, spas, and fitness facilities. It includes specifications, mounting options, control settings, and serviceability details. The unit features dual blowers, a heat recovery core, and automatic defrost. Installation must comply with local building codes and compatibility with other mechanical equipment must be confirmed.
The SHR 8005R is available in two models: SHR 8005R and SHR 14105R, differing in blower count and size. Both models use 120V, single-phase power and include MERV1 filters with optional MERV6 upgrades. The unit can be mounted on a rod or platform and has flanged duct connections. Controls include a three-position rocker switch compatible with Fantech HRV controls.
| Volts | 120V |
|---|---|
| Amperage | 5.4 Amps Total |
| Weight | 80.3 Kg (177 Lbs) |
| Blowers | Two (2) maintenance-free Ebm-Papst™ backward inclined motorized impellers |
| Heat Recovery Core | Fixed plate cross-flow heat exchanger using 1100 alloy aluminum |
| Filters | MERV1 washable filters, optional MERV6 |
| Case Material | 20 gauge G90 galvanized steel with baked powder paint |
| Insulation | 25mm (1 inch) and 50mm (2 inch) foil-faced polystyrene foam |
It is designed for high humidity applications such as indoor swimming pools, spas, fitness facilities, locker rooms, and health centers.
It can be rod mounted or seated on a platform, with flanged connections for ductwork.
It includes an external three-position (Low/Standby/Medium) rocker switch compatible with all Fantech HRV controls.