This manual provides instructions for installing and maintaining the Model 5600 and 5600 Econominder® water treatment equipment.
This service manual provides instructions for the Model 5600 and 5600 Econominder water treatment units. It includes detailed procedures for installation and start-up for the main unit, backwash filter, and Econominder meter. The document also outlines specific valve positions and cycle times for various operational modes.
| Minimum Water Pressure | 25 psi (1.7 bar) |
|---|---|
| Maximum Water Pressure | 120 psi (8.2 bar) |
| Maximum Water Temperature | 110°F (43°C) |
| Minimum Drain Pipe Size | 1/2" (13 mm) |
| Recommended Drain Line Size | 3/4" (19 mm) |
A minimum of 25 psi (1.7 bar) of water pressure is required for the regeneration valve to operate effectively.
The backwash cycle lasts for 15 minutes when using a filter piston.