Mercer Valve Company, Inc. 9100 Series Threaded Safety Relief Valves Installation, Operation and Maintenance Manual

This manual describes the installation, operation, and maintenance of the Mercer Valve Company's 9100 Series Threaded Safety Relief Valves.


Mercer Valve Company, Inc. 9100 Series Threaded Safety Relief Valves Installation, Operation and Maintenance Manual - cover page
Brand
Mercer Valve Company, Inc.
Document type
Service Manual
Language
English
Pages
11
File format
PDF
File size
380 KB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
3520163FA9A7E80731F1CE1E35E949FA

About this manual

This manual provides detailed instructions for installing, operating, and maintaining Mercer Valve Company's 9100 Series Threaded Safety Relief Valves. It covers proper installation orientation, piping requirements, and safety precautions to prevent valve failure. The document also includes step-by-step procedures for disassembly, inspection, cleaning, and reassembly of the valve components, including measurements for orifice sizes and disk stem checks. Maintenance steps include spring inspection, seat and disk polishing, and setting procedures using calibrated test gauges. Safety warnings are emphasized, especially regarding seal wire integrity and proper setting procedures to avoid damage or malfunction.

What's inside

  • Installation
  • Operation
  • Disassembly
  • Inspection and Cleaning
  • Reassembly
  • Setting Procedures
  • Maintenance

Specifications

Set Pressure MarginAt least 15% above operating pressure
Valve Rating StandardAPI 527 bubble-tight test
Maximum LiftMinimum lift per NB-18

Frequently asked questions

What is the recommended set pressure for the valve?

Set the safety relief valve to open at least 15% above the operating pressure where possible.

What happens if the seal wire is broken?

Breaking the seal wire invalidates the manufacturer’s warranty and the valve will be considered a non ASME code valve until repaired by a VR certified shop.

What materials are required for valve setting?

Gas/vapor valves should be set with air; liquid valves should be set using water. Mercer recommends 1 cubic foot capacity below the valve for gas/vapor valves.