This user manual provides the operating instructions for Ezi-IO CC-Link IE TSN DIO products, including safety and installation precautions, product composition, product specifications, exterior names and functions, external wiring diagrams and more.
This user manual provides instructions for safely installing and operating the FASTECH Ezi-IO CC-Link IE TSN DIO. It includes safety precautions, product specifications, wiring diagrams, and configuration steps for CC-Link IE TSN communication. The device supports various input/output models and requires proper setup for operation with PLCs and network systems.
The manual details physical specifications, environmental conditions, and electrical parameters. It also explains how to configure the device using a CPU module and communication master module, including setting IP addresses and network parameters for proper integration into a control system.
| Communication Method | CC-Link IE TSN |
|---|---|
| Physical Layer | Ethernet – 100BASE-TX |
| Connector | RJ45 |
| Communication Speed | 1 Gbps |
| Operating Temperature | 0~50 ℃ |
| Input Voltage | DC24V±10% |
| Input Current | 5mA/points |
| Output Voltage | DC24V |
| Output Current | 0.5A/CH (3A/COM) |
| Isolation Method | Photocoupler isolation |
| Response Time (Off → On) | Under 10μs |
| Response Time (Off → Off) | Under 70μs |
Ezi-IO CC-Link IE TSN DIO.
Maximum 150mA for control power and 110mA for input/output power.
0 to 50°C when in use.
1 Gbps.