This document is the operating instructions for Eutech 2-wire Conductivity Transmitter.
This document provides operating instructions for the Eutech ECCONXTR 2-wire conductivity transmitter. It covers installation, electrical connections, and calibration procedures using standard solutions. The transmitter outputs 4-20 mA and is housed in an IP65 enclosure. Calibration involves adjusting trimmers for zero and full-scale current outputs based on conductivity values.
The manual also lists compatible sensors and accessories for other transmitter models, including pH, ORP, dissolved oxygen, and temperature, and includes ordering information for related components.
| Model | ECCONXTR |
|---|---|
| Range | 0.00 TO 20.00 mS |
| Accuracy | 2% Full Scale |
| Input | 3-wire (2-wires for Conductivity cell; 1 wire for Thermistor) |
| Output | 4-20 mA |
| Operating Voltage | DC 12 V to 24 V |
| Load | 100 Ohms max. for 12 V; 600 Ohms max. for 24V |
| Housing | 77 x 77 x 28 mm, field mountable |
The output is 4-20 mA.
mA = {(16/20) x Conductivity value of Standard soln} + 4mA.
DC 12 V to 24 V.
77 x 77 x 28 mm, field mountable.