This quick start guide describes how to install the DURApulse GS4 AC Drive.
This guide provides installation instructions and safety precautions for the DURA GS4 AC Drive. It covers grounding requirements, capacitor discharge procedures, and static protection for internal components. Wiring diagrams are included for minimal and recommended safety configurations, including STO (Safe Torque Off) wiring and control circuit connections. The guide also addresses voltage and current ratings, environmental conditions, and RFI jumper removal for floating power systems.
| Nominal Supply Voltage | ≤240V AC for GS4-2xxx models, ≤480V AC for GS4-4 models |
|---|---|
| Nominal Supply Current | ≤5kA RMS for ≤40hp models, ≤10kA RMS for ≥40hp models |
| Operating Temperature | –25°C to +75°C |
| Relative Humidity | 0% to 90% without condensation |
Disconnect factory jumpers and wire a safety relay, safety PLC, or E-Stop pushbutton with two N.C. contacts to SCM1 and SCM2 terminals.
Nominal supply voltage should be less than or equal to 240 volts AC.
Use an inverter-rated motor with an insulation rating of 1600 volts.