This document is a manual for a power socket tester.
This manual provides instructions for using the Elma TE-SE500 socket and earth loop tester. It explains how to connect the device, interpret LED indicators, and measure earth electrode impedance and phase-neutral voltage. Safety precautions are emphasized, including handling live circuits and proper maintenance. The device is designed for use with 230 V AC Schuko sockets in TT earthing systems.
The tester displays voltage, impedance, and wiring faults through LED indicators. It includes safety certifications and compliance with European standards. Users must be trained and qualified to operate the device safely. Regular cleaning and inspection are required before use.
| Earth Electrode Impedance Measurement Range | 0.0 Ω to 2000 Ω |
|---|---|
| Earth Electrode Impedance Display Resolution | 0.0 Ω to 2.00 kΩ |
| Current | 18 mA~ |
| Phase-Neutral Voltage Measurement Tolerance | ±4 V~ |
| Operating Temperature Range | -20 °C to +40 °C |
| Maximum Relative Humidity | 80% at 31°C, decreasing linearly to 50% at 40°C |
| Safety Rating | 300 V~ CAT III, reinforced insulation, class 2, pollution degree 2 |
| IP Rating | IP2X |
| Power Supply | From tested power socket (no cell, accumulator or battery) |
| Mains Supply Voltage Fluctuation | -15% / +10% (230 V~ - 240 V~) |
The earth electrode impedance measurement range is from 0.0 Ω to 2000 Ω.
The current rating is 18 mA~, compatible with 30 mA~ RCD.
The safety rating is 300 V~ CAT III, reinforced insulation, class 2, pollution degree 2.
The TE-SE500 is compatible with single-phase 2-pole + earth “Schuko” F-type power sockets (typically installed in Germany), 230 V~ - 240 V~, 50 Hz, wired to a TT earth system.