This is a design guideline file that provides standards and requirements for storefront system design.
This document serves as a design guideline for the Designer of Record (DOR) regarding entrances, storefronts, and curtain walls. It establishes UA standards of work to ensure compliance with contract documents and facilitates the design process by defining specific criteria for structural resistance, air leakage, water resistance, and thermal performance. The guidelines mandate that systems withstand various loads, including wind, seismic, and dynamic forces, and must meet specific testing standards such as ASTM E330 and AAMA 1503.
| Minimum Wind Design Pressure | Maximum components and cladding design pressure (MCCDP) or 50 psf, whichever is greater |
|---|---|
| Deflection Normal to Glazing Plane | 1/175 of clear span for spans up to 13 feet 6 inches |
| Deflection Parallel to Glazing Plane | Reduces glazing bite to less than 75 percent of design dimension |
| Structural Resistance Test Pressure | 150% of the wind design pressure |
| Maximum Air Leakage | .06 cfm/sq. ft. |
| Condensation Resistance Factor | Minimum of 50 |
| Thermal Transmittance | Not exceed .45 BTU/(sf*hr*deg F˚) |
| Warranty Duration | Five (5) years |
The minimum specified design pressure shall be the maximum components and cladding design pressure (MCCDP) or 50 psf, whichever is greater.
The maximum air leakage shall be .06 cfm/sq. ft. when tested according to ASTM E283.
The warranty covers five (5) years against defects in material or workmanship under normal use.
Unless approved otherwise, the finish shall match UA Standard Color, 'Antique White'.