EE850 is a CO2, humidity and temperature duct sensor for various HVAC and ventilation systems, as well as other applications where measurement of air temperature, humidity and CO2 concentration is required. The sensor features a split probe with built-in RH and T sensing elements and a remote CO2 sensing cell. The probe can be inserted directly into a duct for convenient installation.
This document provides installation, connection, and configuration instructions for the Epluse EE850 duct sensor. It measures CO2, humidity, and temperature using non-dispersive infrared technology. The sensor requires proper mounting and cable connections to ensure accurate readings. Users can adjust output signals and scales using a USB configuration adapter and software. Technical specifications include measurement ranges, accuracy, and response times for each parameter.
The EE850 supports digital communication via RS485 with Modbus RTU or BACnet MS/TP protocols. It can be configured for different output types (voltage or current) and scales. The device is designed for industrial environments and must be installed with proper airflow direction and sealed enclosures to prevent measurement errors.
| CO2 Measurement Range | 0...2000 / 5000 / 10000 ppm |
|---|---|
| CO2 Accuracy at 25°C | < ± (50 ppm +2% of measured value) for 0...2000 ppm |
| Temperature Working Range | -20...60 °C (-4...140 °F) |
| Relative Humidity Working Range | 0...95 % RH |
| Temperature Accuracy at 20°C | ±0.3 °C (±0.54 °F) |
| Response Time (CO2) | < 100 seconds at 3 m/s air speed |
| Output Types | Voltage (0-5V/0-10V) or Current (4-20mA) |
| Digital Interface | RS485 with Modbus RTU or BACnet MS/TP |
| Enclosure Protection Class | IP65 |
| Power Supply | 24 V AC/DC ± 20 % or 15-35 V DC |
The CO2 measurement range is 0...2000 / 5000 / 10000 ppm.
The temperature accuracy at 20°C is ±0.3 °C (±0.54 °F).
The device supports RS485 with Modbus RTU or BACnet MS/TP protocols.