EE850 is a CO2, humidity and temperature duct sensor for various HVAC and ventilation systems, as well as other applications where measurement of air temperature, humidity and CO2 concentration is required. The sensor features a split probe with built-in RH and T sensing elements and a remote CO2 sensing cell. The probe can be inserted directly into a duct for convenient installation.


Epluse EE850 CO2, Humidity and Temperature Duct Sensor User Manual - cover page
Brand
Epluse
Document type
User Manual
Language
English
Pages
6
File format
PDF
File size
1.9 MB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
AEAE97B6B7E5C08B30B19F0E16181525

About this manual

This document provides installation, connection, and configuration instructions for the Epluse EE850 duct sensor. It measures CO2, humidity, and temperature using non-dispersive infrared technology. The sensor requires proper mounting and cable connections to ensure accurate readings. Users can adjust output signals and scales using a USB configuration adapter and software. Technical specifications include measurement ranges, accuracy, and response times for each parameter.

The EE850 supports digital communication via RS485 with Modbus RTU or BACnet MS/TP protocols. It can be configured for different output types (voltage or current) and scales. The device is designed for industrial environments and must be installed with proper airflow direction and sealed enclosures to prevent measurement errors.

What's inside

  • Installation
  • Connection Diagrams
  • Technical Data
  • Setup and Adjustment
  • Digital Settings
  • Modbus RTU Example

Specifications

CO2 Measurement Range0...2000 / 5000 / 10000 ppm
CO2 Accuracy at 25°C< ± (50 ppm +2% of measured value) for 0...2000 ppm
Temperature Working Range-20...60 °C (-4...140 °F)
Relative Humidity Working Range0...95 % RH
Temperature Accuracy at 20°C±0.3 °C (±0.54 °F)
Response Time (CO2)< 100 seconds at 3 m/s air speed
Output TypesVoltage (0-5V/0-10V) or Current (4-20mA)
Digital InterfaceRS485 with Modbus RTU or BACnet MS/TP
Enclosure Protection ClassIP65
Power Supply24 V AC/DC ± 20 % or 15-35 V DC

Frequently asked questions

What is the measurement range for CO2?

The CO2 measurement range is 0...2000 / 5000 / 10000 ppm.

What is the accuracy of temperature measurement at 20°C?

The temperature accuracy at 20°C is ±0.3 °C (±0.54 °F).

What is the digital communication protocol?

The device supports RS485 with Modbus RTU or BACnet MS/TP protocols.