This manual provides installation procedures and basic operating instructions for TUF-2000 Series Ultrasonic Flow/Heat Meters
The TUF-2000 Series Ultrasonic Flow/Heat Meters utilize the transit-time principle to measure the velocity of relatively clean liquids in full pipes. The system consists of a converter and transducers, available in various mounting types including separated, fixed, and module configurations.
The guide details the installation of different transducer types (clamp-on, insertion, and inline) and provides wiring diagrams for the converter. It also covers operation procedures, menu settings for parameter selection and meter reading, and specific steps for checking installation quality using signal strength and transmission time ratio.
| Measuring Principle | transit-time principle |
|---|---|
| Application | relatively clean liquids in full pipes |
| Cable Length Limit | 200m |
| Signal Strength Requirement | > 60.0 |
| Signal Quality Requirement | Q > 60 |
| Transmission Time Ratio Range | 97% ~ 103% |
The length of cables between the converter and transducer should not exceed 200m.
The transmission time ratio should be between 97% and 103%.