This user manual provides detailed installation and operation instructions for TUF-2000 Series Ultrasonic Flow/Heat Meters
This manual provides step-by-step instructions for installing and operating T3-1's TUF-2000 Series ultrasonic flow and heat meters. It covers different converter types (separated, fixed, module) and transducer types (clamp-on, insertion, inline), along with wiring diagrams and setup procedures. The guide also explains how to check signal strength and transmission time ratio for proper installation.
The manual includes sections on mounting, wiring, parameter setup, and troubleshooting, with specific instructions for each type of installation. It emphasizes using manufacturer-provided cables and keeping cable lengths under 200m for optimal performance.
It measures velocity of relatively clean liquids in full pipes using transit-time principle.
It consists of a Converter and a transducer.
It should be between 97% and 103%.
Signal strength must be greater than 60.0.