This manual introduces the design principle, operation and maintenance of F7000/8000 series.
This document serves as a comprehensive guide for the maintenance and operation of Flow Safe F7000 and F8000 Series pilot-operated safety relief valves. It covers general safety warnings, installation procedures, and startup protocols. The manual details the specific operational differences between conventional tubed pilot valves and Integral Module (IM) construction models, explaining how system pressure acts on the main valve piston to control flow.
| Pilot valve MAWP (F100) | 740 psig |
|---|---|
| Recommended softgoods replacement interval | Every three years |
| Corrosion allowance for carbon steel | 0.06 inch (1.5 mm) |
| F200 blowdown adjustment range | 3% to 20% of set pressure |
It is recommended to replace softgoods every three years, though customers should determine their own schedule based on use and environment.
Cycling the valve at least once a year is considered good practice to verify operation and confirm parts are not seized.
Repairs should be performed by FLOW SAFE, Inc., or by a National Board-certified valve repair shop holding a "VR" (Valve Repair) stamp.