The DMP XR200 Command Processor is a versatile 12 VDC combined burglary and fire communicator panel with battery backup. It provides eight on-board burglary zones and two on-board 12 VDC Class B powered zones with reset capability for 2-wire smoke detectors or other latching devices.

What's inside

  • Product Specifications
  • Panel Features
  • System Components
  • Installation
  • Primary Power Supply
  • Secondary Power Supply
  • Bell Output
  • Keypad and Zone Expander Bus
  • Smoke and Glassbreak Detector Output
  • Dry Contact Relay Outputs

Specifications

Transformer Input16.5 VAC 40VA
Standby Battery12 VDC 6.5A
Auxiliary Output12 VDC output at 1 Amp
Bell Output12 VDC at 1.5 Amp
On-board Burglary ZonesEight 1k Ω EOL burglary zones
Powered ZonesTwo 3.3k Ω EOL Class B (Style A) powered zone
Keypad Data Bus CapacityUp to eight supervised keypads or expanders
Relay OutputsTwo SPDT relay outputs
Auxiliary Voltage OutputsEight auxiliary 12 VDC, 50mA resistive outputs

Frequently asked questions

What is the transformer input requirement for the XR200?

The transformer input requires 16.5 VAC at 40VA.

How many on-board burglary zones does the XR200 provide?

The panel provides eight on-board burglary zones with 1k Ω EOL resistors.

Can the XR200 operate as a local panel?

Yes, the XR200 can operate as a local panel.

What is the capacity of the Keypad Data Bus?

You can connect up to eight supervised keypads or expanders to the bus.