This service manual provides maintenance information for indoor and outdoor units.
This service manual provides technical information for CEI air conditioner indoor and outdoor units, including models CEI09CD, CEI12CD, CEI18CD, and CEI24CD. It contains product dimensions, refrigeration cycle diagrams, and detailed operation instructions for various modes such as cooling, heating, dry, sleep, and turbo.
| Indoor Unit Dimensions (CEI09CD) | 698 x 190 x 255 mm |
|---|---|
| Indoor Unit Dimensions (CEI24CD) | 1186 x 260 x 340 mm |
| Outdoor Unit Dimensions (CEI09CD) | 700 x 552 x 256 mm |
| Outdoor Unit Dimensions (CEI24CD) | 845 x 607 x 326 mm |
| Compressor Safety Delay | 3 minutes |
| 4-way Valve Safety Delay | 2 minutes |
| Lower Voltage Protection Threshold | 158V |
| Over Voltage Protection Threshold | 260V |
| Indoor Exchanger Overheat Protection | 55°C |
The compressor is ceased for 3 minutes before restarting to balance the pressure in the refrigeration cycle.
The unit shuts down when the AC voltage is 158V or lower and remains at that level for 10 seconds.
The unit enters indoor exchanger overheat protection, and the compressor frequency drops until the temperature is 52°C or lower.