This manual provides detailed information about the features and usage of the ADAM-5000 series I/O modules.
This manual introduces the detailed specifications, functions, and application wiring for the ADAM-5000 Series I/O modules. Advantech provides 19 types of these modules to interface ADAM-5510 Series Controllers with various field devices and processes. The document covers analog input, analog output, digital I/O, relay output, counter/frequency, and serial communication modules.
| Isolation Voltage | 3,000 V |
|---|---|
| Initialization Time (per module) | 5 seconds |
| Total Initialization Time (4 slots) | about 20 seconds |
| Calibration Range | 0-20 mA and 4-20 mA |
The initialization time of each ADAM-5013 module is 5 seconds due to the conversion time required by the A/D converter.
The modules provide opto-isolation and transformer-based isolation up to 3,000 V to protect equipment from ground loops and power surges.
Calibration involves applying power for 30 minutes, connecting a meter, issuing commands for 4 mA and 20 mA, and using the Trim option to adjust the output.