This manual describes the causes of conductor and shield wire damage, the types of common damage and failures, the inspection and assessment of damage, recommendations for the restoration of the conductor and finally, preventative measures to avert future damage.
This manual serves as a guidebook for the inspection and repair of damaged or worn conductors on transmission lines. It details the causes and types of conductor damage, including aeolian vibration, galloping, and wake-induced oscillations, explaining the physical mechanisms behind strand fatigue and failure.
Aeolian vibration is created by smooth winds blowing across the conductor surface at speeds between 5 and 15 mph.
The frequency of aeolian vibration for overhead shield wires is generally between 40 and 130 hertz.
Galloping is generally associated with moderate to high winds blowing over ice-covered conductors at speeds between 15 and 40 mph.
It is necessary to relieve the line tension on the conductor at the support during a visual inspection.