Laurel Electronics QLS Quad Output 4-20 mA Current Loop Splitter / Retransmitter User Manual

QLS Quad Output 4-20 mA Current Loop Splitter / Retransmitter With ±10V common mode isolation between input & outputs


Laurel Electronics QLS Quad Output 4-20 mA Current Loop Splitter / Retransmitter User Manual - cover page
Brand
LAUREL Electronics
Document type
User Manual
Language
English
Pages
8
File format
PDF
File size
358 KB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
212B52011C25948C712B606575C02582

About this manual

The QLS is a quad-output 4-20 mA current loop splitter/retransmitter that generates four independently adjustable 4-20 mA outputs from a single input source (4-20 mA, 1-5V, 0-5V, or 0-10V). It features ±10V common-mode isolation between input and outputs, allowing operation in different grounding environments. The device supports two power options: QLS-1 (85-264 Vac) and QLS-2 (10-48 Vdc or 12-32 Vac). Each output includes potentiometers for zero and span adjustment, a yellow LED for loop continuity, and a current test point for measurement without breaking the loop. The unit is designed for industrial applications and includes safety and environmental specifications for proper operation.

What's inside

  • Ordering Guide
  • Product Description
  • Receiving & Unpacking
  • Safety Considerations
  • Jumper Settings
  • Electrical Connections
  • Setting & Calibration
  • Specifications
  • Warranty

Specifications

Signal Outputs4 outputs, 4-20 mA sourcing
Power InputQLS-1: 85-264 Vac; QLS-2: 10-48 Vdc or 12-32 Vac
Load Regulation±0.005% of span from 0 to 600 Ω
Accuracy±0.02% max span error at 23°C
Operating Temperature-40°C to 70°C
Weight140 g (5 oz)

Frequently asked questions

How many outputs does the QLS have?

The QLS has four independently adjustable 4-20 mA outputs.

What is the common-mode isolation between input and outputs?

The input and outputs are mutually isolated to ±10V at 600 ohm load.

What power options are available for the QLS?

QLS-1 supports 85-264 Vac, and QLS-2 supports 10-48 Vdc or 12-32 Vac.

Download PDF (358 KB)