Marathon Capacitor Regulated Pancake Generator Troubleshooting Guide

Introduces the troubleshooting methods of pancake generator


Marathon Capacitor Regulated Pancake Generator Troubleshooting Guide - cover page
Brand
Marathon
Category
Generator
Document type
Service Manual
Language
English
Pages
7
File format
PDF
File size
286 KB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
E829DEB2925A8B810830BF1C990B8FFC

About this manual

This troubleshooting guide addresses common causes of very low or no output voltage in Marathon capacitor regulated pancake generators, specifically models 201CSA5411 (6kW) and 201CSA5420 (8kW). The document outlines a systematic diagnostic process involving six main components: the main stator winding, main rotor winding, excitation winding, capacitor, diode, and surge suppressor. It provides detailed instructions for testing these components using digital or analog multimeters to identify failures that require component replacement or generator replacement.

What's inside

  • Troubleshooting Capacitor Regulated Pancake Generators
  • Check the Capacitor
  • Check the Main Stator Winding
  • Check the Excitation Winding
  • Check for Grounded or Shorted Main Stator Windings
  • Check the Surge Suppressor
  • Checking and Replacing the Diode
  • Field Flashing / Restoring Residual Magnetism

Specifications

Model 201CSA5411 Output6kW
Model 201CSA5420 Output8 kW
Main Stator Winding Resistance.3 to .7 Ohms
Excitation Winding Resistance1.0 to 2.5 ohms
Diode Forward Resistanceunder 100 Ohms
Diode Reverse Resistanceover 30,000 ohms

Frequently asked questions

What tools are needed to troubleshoot these generators?

You will need a good multi-meter (such as a Fluke), a ratchet set, a set of screwdrivers, and a soldering iron.

What causes low or no output voltage in these generators?

Common causes include a failed capacitor, failed main stator or excitation windings, a failed diode, a failed surge suppressor, or a loss of residual magnetic field.

Can failed windings be repaired?

No, failed main stator or excitation windings cannot be repaired and the generator must be replaced.

How do you restore residual magnetism?

You can use a 12V battery to flash the field statically or use a 120V field flash through the service receptacle.