This instruction manual provides detailed instructions on how to use the Typ 8008 flow meter, including installation, operation and maintenance
This manual provides detailed instructions for installing, operating, and maintaining the Typ 8008 flow meter. It covers safety precautions, technical specifications, wiring, calibration, and troubleshooting. The device measures flow and consumption using a calorimetric principle and supports multiple output types including 4–20mA and pulse output. It is designed for compressed air and gases with selectable units and Modbus RTU interface. Proper installation requires adherence to inlet/outlet run specifications to ensure accurate measurements.
| Measuring principle | calorimetric measurement |
|---|---|
| Measuring medium | Air, gases |
| Operating temperature | -30 ... 80°C probe tube -20 ... 70°C housing |
| Operating pressure | up to 16 bar, special version PN 40 (40 bar) |
| Power supply | 18 to 36 VDC |
| Power consumption | max. 5W |
| Digital output | RS 485 (Modbus RTU) |
| Analog output | 4...20 mA (max. burden < 500 Ohm) |
| Pulse output | pulse output potential free (dry contact) passive: max. 48Vdc, 150mA |
| Accuracy | ± 1,5 % m.v., ± 0,3 % f. s.* |
| Display | optional TFT 1.8 Resolution 220 x 176 |
| Mounting thread | R 1/4", R1/2", R3/4", R1", R 1 1/4" R1 1/2", R 2” |
| Material | Stainless steel 1.4301 / 1.4404 |
| Protection class | IP65 |
Up to 16 bar, with a special version available for 40 bar.
The accuracy is ±1.5% of measured value and ±0.3% of full scale.
The probe tube operates from -30°C to 80°C, and the housing from -20°C to 70°C.