Apollo Valves DC4A / DCLF4A Double Check Valve Backflow Preventer Installation, Operation & Maintenance Manual

Introduce Apollo's 1/2” - 2” Double Check Valve (DC) Backflow Preventer Model DC4A / DCLF4A features and usage methods


Apollo Valves DC4A / DCLF4A Double Check Valve Backflow Preventer Installation, Operation & Maintenance Manual - cover page
Brand
Apollo Valves
Document type
User Manual
Language
English
Pages
12
File format
PDF
File size
6.6 MB
Published
17 October, 2023
Updated
17 October, 2023
MD5 checksum
F6F519F13B2121CDDCEB860CA1C87A4F

About this manual

This manual provides step-by-step instructions for installing, operating, troubleshooting, and maintaining the Apollo Valves DC4A and DCLF4A double check valve backflow preventers. It covers assembly, disassembly, testing procedures, and maintenance of the device's components. The manual includes diagrams and detailed part lists for both standard and lead-free versions. Testing procedures are described using a differential pressure gauge test kit, with specific steps for testing each check valve and identifying leaks in shut-off valves.

What's inside

  • Description and Operation
  • Installation
  • Troubleshooting Guide
  • Maintenance Instructions
  • Testing Procedures
  • Parts List
  • Repair Kits

Frequently asked questions

What is the minimum pressure required to initiate flow?

Supply pressure must be sufficient to open both checks and overcome friction, normally a minimum of 3 to 5 psi above the downstream pressure.

What is required to pass the check valve test?

Each check valve must have a minimum of 1.0 psid to pass the test.

How do you test a leaking shut-off valve?

Connect the test kit to test cocks #2 and #3, close shut-off valve #2, and observe the gauge. If the gauge drops to zero psid, the #2 shut-off valve is leaking.