Introduce Apollo's 1/2” - 2” Double Check Valve (DC) Backflow Preventer Model DC4A / DCLF4A features and usage methods
This manual provides step-by-step instructions for installing, operating, troubleshooting, and maintaining the Apollo Valves DC4A and DCLF4A double check valve backflow preventers. It covers assembly, disassembly, testing procedures, and maintenance of the device's components. The manual includes diagrams and detailed part lists for both standard and lead-free versions. Testing procedures are described using a differential pressure gauge test kit, with specific steps for testing each check valve and identifying leaks in shut-off valves.
Supply pressure must be sufficient to open both checks and overcome friction, normally a minimum of 3 to 5 psi above the downstream pressure.
Each check valve must have a minimum of 1.0 psid to pass the test.
Connect the test kit to test cocks #2 and #3, close shut-off valve #2, and observe the gauge. If the gauge drops to zero psid, the #2 shut-off valve is leaking.