This manual introduces the web browser configuration, utility software, protocols and operating modes, modules and register maps of the D7000 series products.
The DGH D7000 series consists of a family of Ethernet-based data acquisition modules designed for industrial process control. The product line includes multi-channel analog input modules (voltage, current, thermocouple), analog output modules, and discrete digital I/O modules that communicate via Modbus TCP/IP and REST protocols.
The document provides detailed instructions on web browser configuration, utility software usage, protocol functions, and register maps for various module types. It also includes specific calibration procedures for analog inputs and outputs, as well as information on factory resets and static IP address setup.
| Input Channels (Analog) | Seven differential input channels |
|---|---|
| Voltage Measurement Ranges | +/-25mV, +/-50mV, +/-100mV, +/-1V, +/-5V and +/-10V |
| Current Measurement Range | +/-20mA input range |
| Thermocouple Types Supported | J, K, T, E, R, S, B and C types |
| Digital Input Pull-up Resistors | Internal 22K ohm pull-up resistors |
| Digital Output Voltage Rating | Up to 30Vdc |
| Digital Output Sink Current | 100mA per bit |
The modules communicate using Modbus TCP/IP protocol and the REST (Representational State Transfer) protocol.
IP addresses can be specified as either a Static address assigned by the user or automatically via DHCP.
No, all setups are performed from the outside and there are no user-serviceable parts inside.