This is a quick reference guide for Hitachi SJ300 series inverters. It contains information on product installation, use, and maintenance.
This document serves as a quick reference guide for the Hitachi SJ300 Series Inverter, intended specifically for experienced users maintaining existing installations. It covers UL and CE version models with three-phase input voltages of 200V and 400V classes.
The guide provides critical technical data including wiring warnings, terminal tightening torque values, wire sizes, fuse and circuit breaker ratings, and motor overload protection settings. It also details control circuit terminals, serial port configurations, analog input/output functions, programming error codes, and the auto-tuning procedure.
| Input Voltage Class | Three-phase Input 200V and 400V |
|---|---|
| Document Type | Quick Reference Guide for experienced users |
| Wire Warning (Suffix L) | Not more than 100,000 rms symmetrical amperes, 240 V maximum |
| Wire Warning (Suffix H) | Not more than 100,000 rms symmetrical amperes, 480 V maximum |
| Overload Protection Range | 0.2 * rated current to 1.2 * rated current |
| Analog Output FM Range | 0 to max. frequency in Hz |
It is intended for reference use by experienced users in servicing existing installations.
Users must use 60/75°C Cu wire only or equivalent.
No, when two or more motors are connected to the inverter, they cannot be protected by electronic overload protection.
It is important to auto-tune during initial installation and after replacing either the motor or the inverter.