IPC600 unbalance load self-switching system is a device developed by our company to solve the problem of unbalanced load in distribution network. The device uses real-time uninterruptible re-distribution of single-phase load, which can control the current imbalance within 5%, which solves the problem of current imbalance better and can be widely used in China's distribution network projects.
The IPC600 Unbalanced Load Self-Switching System is designed to solve three-phase load imbalance issues in low-voltage distribution networks. It consists of a main control unit and intelligent phase switching units that automatically monitor and redistribute single-phase loads to maintain balance within 5% without interrupting power supply.
The system utilizes carrier wave communication for data exchange between the main controller and switching terminals, eliminating the need for additional wiring. Key features include zero-crossing switching technology with a switching time of less than 2ms, intelligent fault phase switching to minimize downtime, and support for multiple communication protocols such as ModBus-RTU, IEC60870-5-103, and IEC61850. This manual is written in Chinese.
| Rated Voltage | AC380V |
|---|---|
| Voltage Deviation Allowance | -10%~+10% |
| Switching Load Capacity (IPC601) | 60A |
| Switching Load Capacity (IPC602) | 200A |
| Operating Temperature Range | -25℃~+55℃ |
| Protection Rating | IP54 |
| Power Consumption (Normal Operation) | Not more than 6W |
The system effectively controls current unbalance within 5%. The text states: '有效的把电流不平衡度控制在5%以内'.
The device uses zero-crossing switching technology to ensure a switching time of less than 2ms. The text states: '换相时间控制在2ms以内'.
The device supports ModBus-RTU, IEC60870-5-103, and can be extended to meet IEC61850 requirements. The text states: '主控单元可支持多种通信规约,如ModBus-RTU协议、IEC60870-5-103协议以及...IEC61850协议'.