This manual provides installation instructions for the ProReact Digital Sensor Control Unit (DSCU-EN). The unit can be used for a variety of applications, including fire detection, intrusion detection, and building automation. It supports two-wire RS-485 Modbus RTU/ASCII communications.
The Thermocable ProReact Digital Sensor Control Unit (DSCU-EN) is a dual zone module designed to monitor up to two zones of Thermocable ProReact EN Digital Linear Heat Detection (LHD) Cable. When an overheat or fire situation triggers either zone, the unit automatically calculates and displays the distance along the cable to the alarm point in feet and metres. The unit is intended to be installed between the Digital Linear Heat Detection cable and a conventional or addressable fire alarm control panel.
| Enclosure Dimensions | H180mm x W120mm x D60.5mm |
|---|---|
| Operating Voltage | 12Vdc — 24Vdc — 36Vdc |
| Operating Temperature Range | -20°C – +50°C |
| Max Zone Length | 1000m |
| End of line resistor | 3.6kohm |
| Alarm Output Frequency | 2.4kHz |
Do not exceed the maximum operating voltage of the DSCU-EN (36Vdc).
Ensure the end of line resistor (3.6kohm) is securely connected at the end each linear heat detection cable.
Yes, the two zones can operate independently of each other, or in interlock mode.