Thermocable DSCU-EN Digital Sensor Control Unit Installation Manual

This manual provides installation instructions for the ProReact Digital Sensor Control Unit (DSCU-EN). The unit can be used for a variety of applications, including fire detection, intrusion detection, and building automation. It supports two-wire RS-485 Modbus RTU/ASCII communications.


Thermocable DSCU-EN Digital Sensor Control Unit Installation Manual - cover page
Brand
Thermocable
Category
Other Electronics
Document type
Installation Guide
Language
English
Pages
17
File format
PDF
File size
1.9 MB
Published
16 October, 2023
Updated
16 October, 2023
MD5 checksum
041E17D95222E46FB44F65B8B9536BCA

About this manual

The Thermocable ProReact Digital Sensor Control Unit (DSCU-EN) is a dual zone module designed to monitor up to two zones of Thermocable ProReact EN Digital Linear Heat Detection (LHD) Cable. When an overheat or fire situation triggers either zone, the unit automatically calculates and displays the distance along the cable to the alarm point in feet and metres. The unit is intended to be installed between the Digital Linear Heat Detection cable and a conventional or addressable fire alarm control panel.

What's inside

  • Important Guidelines
  • General Overview
  • Technical Specifications
  • Overview
  • Connections Diagram
  • Operating Modes
  • Wiring Diagram: Independent
  • Wiring Diagram: Interlock
  • Leader Cable
  • Commissioning

Specifications

Enclosure DimensionsH180mm x W120mm x D60.5mm
Operating Voltage12Vdc — 24Vdc — 36Vdc
Operating Temperature Range-20°C – +50°C
Max Zone Length1000m
End of line resistor3.6kohm
Alarm Output Frequency2.4kHz

Frequently asked questions

What is the maximum operating voltage for the DSCU-EN?

Do not exceed the maximum operating voltage of the DSCU-EN (36Vdc).

What resistor is required at the end of the linear heat detection cable?

Ensure the end of line resistor (3.6kohm) is securely connected at the end each linear heat detection cable.

Can the DSCU-EN zones operate independently?

Yes, the two zones can operate independently of each other, or in interlock mode.