This document is a user manual for the DGC5 Digital Gas Controller
The INTEC Controls DGC5 Digital Gas Controller is designed for monitoring and warning of toxic and combustible gases and vapors in ambient air. It fulfills requirements for stationary monitoring in locations such as underground garages, tunnels, and industrial ranges. The device supports up to 98 digital transmitters via RS-485 communication and features up to 30 potential-free change-over contact relays for alarm transmission.
Configuration and operation are performed via a logical menu structure driven by a keypad and LCD display. The system includes four password levels to protect settings against unauthorized intervention, ranging from operator functions to service technician access. Key features include normal, alarm, and fault modes, with options for latching or automatic reset based on gas concentration thresholds.
| Max Digital Transmitters | 98 |
|---|---|
| Max Analog Transmitters | 48 |
| Communication Protocol | RS-485 |
| Max Relays | 30 |
| Contact Type | Potential-free change-over |
| Input Signal Range | 3 mA - 22 mA |
The controller is used for monitoring and warning of toxic and combustible gases and vapors, including carbon monoxide, nitrogen dioxide, and freons.
Configuration is menu-driven via the keypad, requiring a valid four-digit numeric code to access specific settings.
Yes, the alarm is automatically reset when the gas concentration falls below the alarm threshold and hysteresis, unless latching mode is active.