INTEC Controls DGC5 Digital Gas Controller User Manual

This document is a user manual for the DGC5 Digital Gas Controller


INTEC Controls DGC5 Digital Gas Controller User Manual - cover page
Brand
Intec Controls
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
31
File format
PDF
File size
1 MB
Published
16 October, 2023
Updated
16 October, 2023
MD5 checksum
D8FCCA8C32153F290477CD4113019E9A

About this manual

The INTEC Controls DGC5 Digital Gas Controller is designed for monitoring and warning of toxic and combustible gases and vapors in ambient air. It fulfills requirements for stationary monitoring in locations such as underground garages, tunnels, and industrial ranges. The device supports up to 98 digital transmitters via RS-485 communication and features up to 30 potential-free change-over contact relays for alarm transmission.

Configuration and operation are performed via a logical menu structure driven by a keypad and LCD display. The system includes four password levels to protect settings against unauthorized intervention, ranging from operator functions to service technician access. Key features include normal, alarm, and fault modes, with options for latching or automatic reset based on gas concentration thresholds.

What's inside

  • Application Intended for Use
  • Description
  • Normal Mode
  • Alarm Mode
  • Fault Mode
  • Keypad User Interface
  • Setting Parameters
  • Code Levels
  • Fault Management
  • Menu Overview

Specifications

Max Digital Transmitters98
Max Analog Transmitters48
Communication ProtocolRS-485
Max Relays30
Contact TypePotential-free change-over
Input Signal Range3 mA - 22 mA

Frequently asked questions

What gases can the DGC5 monitor?

The controller is used for monitoring and warning of toxic and combustible gases and vapors, including carbon monoxide, nitrogen dioxide, and freons.

How are parameters changed on the DGC5?

Configuration is menu-driven via the keypad, requiring a valid four-digit numeric code to access specific settings.

Can the alarm be reset automatically?

Yes, the alarm is automatically reset when the gas concentration falls below the alarm threshold and hysteresis, unless latching mode is active.