Sure-Aire™ Flow Monitoring System is an instrument for monitoring air, with NEMA-4 / IP56 enclosure rating, factory calibrated, 24 VDC / 24 VAC or 100-240 VAC 50 / 60 Hz input voltage, 4-20 mA 2-10 VDC isolated output transmitter, BACnet MSTP Modbus communication protocols.
The document provides instructions for installing, operating, and maintaining the Sure-Aire Electronics Flow Monitoring System. It details safety precautions, hardware requirements, and environmental specifications for the device used to monitor differential pressure or volume flow in fans.
Key features include NEMA-4/IP56 enclosure ratings, factory calibration, support for 24 VDC/AC or 100-240 VAC inputs, and isolated output transmitters (4-20 mA or 2-10 VDC). The system supports communication protocols such as BACnet MSTP and Modbus, includes an LCD touch panel interface, and offers temperature compensation for air density.
| Enclosure Rating | NEMA-4 / IP56 |
|---|---|
| Input Voltage | 24 VDC / 24 VAC or 100-240 VAC 50 / 60 Hz |
| Output Signal | 4-20 mA or 2-10 VDC |
| Communication Protocols | BACnet MSTP, Modbus |
| Flow Accuracy | +/- 3.0% of actual flow |
| Transducer Accuracy | +/- 0.5% of full scale at 77ºF (25ºC) |
| Pressure Limit | 70 psi (1938 in. wg) |
| Operating Temperature Range | -4° to 140°F (-20° to 60°C) |
Installation requires four (4) #8-32 screws and 1/4-inch nylon tubing.
Yes, it includes a remote duct temperature sensor and programmable elevation for air density compensation.
The maximum length for each line of 1/4-inch nylon tubing is 75 feet (23 m).