Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide

This is a manual about the start-up procedure of the second nature type medium temperature refrigeration system. It introduces the start-up program and precautions.


Hill PHOENIX Second Nature Medium Temperature Secondary Refrigeration Start-Up Guide - cover page
Brand
Hill Phoenix
Category
Other Electronics
Document type
User Manual
Language
English
Pages
15
File format
PDF
File size
7.9 MB
Published
16 October, 2023
Updated
16 October, 2023
MD5 checksum
5E6E081794BD36CC460D223E574018E8

About this manual

This document serves as a start-up guide for the Hill PHOENIX Second Nature™ Medium Temperature Secondary Refrigeration System. It outlines critical procedures to ensure safe, effective, and efficient operation of the propylene glycol secondary coolant system following installation.

The manual details four main areas of activity: initial start-up steps involving pressure testing and flushing, adding fluid to the system, setting up balance valves, and establishing system control strategies including pump management. It includes specific instructions for verifying component installation, cycling pumps, adjusting amperage, and managing freeze-points during the transition from water flush to secondary fluid circulation.

What's inside

  • Initial Start-up Procedures
  • Adding Fluid to System
  • Pump Strategy
  • System Operation
  • Warm Fluid Defrost system
  • Rack Floating
  • Disclaimer

Frequently asked questions

What is the required pre-charge pressure in the expansion tank?

The pre-charge pressure in the expansion tank must be verified to be at 12 psig.

What secondary fluid concentration is recommended for the initial fill?

The guide instructs users to pump two drums of 35% Secondary Fluid into the system first, followed by one drum of 100% Secondary Fluid.

What pressure must be maintained in the return fluid line during operation?

Operators must maintain a return fluid pressure at 20 psig by adding water or secondary fluid as needed.

What are the specific cut-in and cut-out temperatures for the warm fluid defrost system?

The master warm fluid balance valve should be set to operate with a cut-in temperature of 65˚F and a cut-out temperature of 75˚F.

Download PDF (7.9 MB)