Avatar Instruments CP Series Power Control Operating Manual

This is the operating manual of CP series power control of Avatar Instruments, Inc. It introduces the features, description, installation, electrical connections, warranty, specifications, troubleshooting, ordering codes, wiring diagrams, dimensional drawings of the product.


Avatar Instruments CP Series Power Control Operating Manual - cover page
Brand
Avatar Instruments
Category
Other Electronics
Document type
User Manual
Language
English
Pages
54
File format
PDF
File size
2.6 MB
Published
16 October, 2023
Updated
16 October, 2023
MD5 checksum
03032B3FCE699ABC6868319B3873F171

About this manual

This manual provides instructions for the installation, operation, and maintenance of Avatar Instruments CP Series SCR power controllers. These multi-zone controllers are designed for phase angle fired or zero voltage switched control of directly connected electric heaters, utilizing 4-20mA input signals and featuring optically isolated circuitry.

What's inside

  • Introduction
  • Features
  • Description
  • Theory of Operation
  • Installation
  • Electrical Connections
  • Options
  • Specifications
  • Troubleshooting
  • Wiring Diagrams

Specifications

Ambient Temperature Ratingup to 50ºC (122ºF)
Input Signal4-20 mA
Maximum Zoneseight separate heating zones
Control MethodPhase angle fired or zero voltage switched
Safety ListingUL 508 listed

Frequently asked questions

What types of loads can the CP series control?

The CP series controls directly connected electric heaters and cannot control transformers or motors.

Is a control transformer required for the CP series?

No, there are no control transformers needed to power any of the trigger boards.

What are the three field replaceable items?

The three field replaceable items are the printed circuit board(s), the dual SCR package, and the MOV (metal oxide varistor) on high powered models.