CXM Digital Heat Pump Controller Application, Operation & Maintenance
The document provides a comprehensive guide for the CXM electronic heat pump control, detailing its features compared to other models like CXM-Lon and CXM-MPC. It outlines general operating parameters, including environmental limits and power requirements, as well as relay contact ratings.
The manual includes instructions on physical installation dimensions, descriptions of LED status indicators and alarm relay operations, and procedures for entering Test Mode. It also covers field configuration options such as low temperature cut-out settings via jumpers and DIP switch configurations for unit performance and DDC outputs.
| Operating Environment Temperature Range | -40°F to 176°F |
|---|---|
| Storage Environment Temperature Range | -40°F to 185°F |
| Normal Power Draw | 5 VA at 24VAC |
| Maximum Power Draw | 9 VA at 24VAC |
| Compressor Relay Rating | 40VA at 24VAC |
| Alarm Relay Rating | 28VA at 24VAC |
Test Mode allows service personnel to check control operation by speeding up all time delays 15 times.
Test Mode can be exited by shorting the test terminals for 3 seconds or by cycling the G input three times within a 60-second period.
Flashing Code 1 indicates that there is no fault in memory.