This is the WaterFurnace FX10 Application Guide, which introduces the FX10 water source heat pump controller's components, input/output configurations, and service procedures
The manual provides information regarding the FX10 Water Source Heat Pump (WSHP) controller designed for units with a nominal capacity of 3/4 to 6 tons. It describes the controller's components, input/output configurations, and necessary service procedures to ensure safe operation.
Key operational features include heating and cooling control via remote sensors or command modules, monitoring of equipment protection controls like high and low pressure refrigerant limits, and sequencing for fan and compressor operations. The document also outlines optional communication boards such as Open N2 (Metasys), LON network, and BACnet.
| Nominal Capacity Range | 3/4 to 6 tons |
|---|---|
| Communication Baud Rate | 19,200 baud rate |
| Temperature Sensor Type | PTC thermistor |
The processor generates a random length program start delay that varies between 1 and 120 seconds.
In Unoccupied mode, the fan is operated in a cycled fashion and remains off unless the zone temperature exceeds specific heating or cooling set points.
The blower volume (CFM) will be reduced by 15% to decrease the dry bulb temperature of the discharge air.