This bulletin is a temporary supplement to the KITCHEN KNIGHT II Technical Manual (PN551274-4) dated March 1, 2006 and is not intended to replace the requirements and limitations outlined in the current manual.
This manual provides instructions for the design, installation, recharge, and maintenance of Pyro-Chem Kitchen Knight II Restaurant Fire Suppression Systems. It is intended for use by individuals who have attended a Pyro-Chem training program and are authorized to install, recharge, design, and maintain these systems.
The document details specific procedures for system cleanup and recharge, including safety precautions for handling wet agents, flushing the piping network, and rebuilding valve components. It also outlines specific nozzle positioning and coverage limitations for the Nieco Broiler Model MPB 94.
| Maximum Heat Input | 109,590 Btu/hr |
|---|---|
| Nozzle Quantity | One |
| Nozzle Type | 2L |
| Nozzle Height | 20 in. (508 mm) |
| Nozzle Location | 6 1/2 in. (165 mm) inside from outside edge |
| Tank Operating Pressure | 225 psi (15.5 bar) |
| Valve Torque | 12.5 ft-lb (16.9 Nm) |
Maintenance must be conducted at six-month intervals, or earlier if the situation dictates.
Twelve-year maintenance must include agent tank hydrostatic testing.
Those responsible for recharge must be trained and hold a current Pyro-Chem certificate in a Kitchen Knight II training program.