Water System Tanks are a precharged diaphragm type vessel which have been manufactured to meet the requirements of ANSI/NSF Standard-61G (for potable water).
The document describes Water System Tanks as precharged diaphragm vessels designed to maintain constant system pressure and minimize pump cycling. It highlights the importance of proper sizing and installation by a qualified professional to ensure safe and trouble-free service.
Key sections include safety warnings regarding electrical shock, detailed installation procedures for both submersible and jet pumps, operation instructions for adjusting air charge and pressure switch settings, and troubleshooting steps for common issues like short cycling or leaks.
The tank pre-charge air pressure should be adjusted to be 2-3 PSIG less than the pump cut-in pressure setting.
The tank should be flushed 5 times prior to household use.
The proper pressure differential between cut-off and cut-in settings would be 20 psi, not exceeding 25 psi.