This manual covers the operation and maintenance of the LP-Gas Vaporizer, an innovative liquid vaporizing and gas mixing solution produced by Algas-SDI. The equipment uses flammable fuel LPG and requires a thorough understanding of the equipment for safe operation and maintenance. Only trained and fully qualified personnel are allowed to service this equipment. When replacing components, it is important to use the same type and model to avoid unpredictable consequences. The UL listing of the unit becomes void if components not approved for use in the UL listed equipment are used. Warranty, copyrights, and approvals are also covered in the manual.
This document serves as the Operations & Maintenance Manual for Algas-SDI Direct Fired Vaporizers, covering models 40/40H, 60/60H, 80/40H, and 120/60H. It details the system's basic features, including burner input ratings and gas consumption rates, and outlines safety warnings regarding flammable gas hazards and electrical disconnection requirements.
The guide provides comprehensive instructions for installation, operation, and maintenance. Key sections include procedures for starting the vaporizer, adjusting the regulator and thermostat, and performing monthly and annual servicing tasks. It also features troubleshooting trees for common issues such as pilot ignition failure and vapor pressure drops, along with detailed parts lists and repair kit information.
| Burner Input (40/40H, 80/40H) | 51,360 BTU's/hr per burner |
|---|---|
| Burner Input (60/60H, 120/60H) | 77,040 BTU's/hr per burner |
| Gas Consumption | 1000 BTU's per gallon of propane vaporized |
| Pilot Burner Input | 2200 BTU's/hr |
| Nominal Operating Temperature | 140 to 160 °F |
| Burner Gas Pressure (40/40H, 80/40H) | 14" W.C. |
| Burner Gas Pressure (60/60H, 120/60H) | 18" W.C. |
Only a trained and fully qualified person should service this equipment.
Refer to the Troubleshooting Tree #1: Pilot Will Not Light section in the manual.