This document introduces the MODBUS-RTU master station communication function of the product series from Lu Jie Technology, Shijiazhuang Lu Jie Electronic Technology Co., Ltd. The document provides detailed instructions on the use of registers and relays, parameter settings, communication timeout flags, and fault detection. It also explains the data sending, receiving, and broadcast sending functions of the master station and slave stations.
This document provides a functional description for the Lu Jie 2N Series MODBUS-RTU master station. It details the configuration of RS485 serial ports, including protocol switching between FX programming and MODBUS-RTU, and the setting of communication parameters such as baud rate, parity, and stop bits via specific data registers (e.g., D8120).
The guide covers the usage of internal registers (M8121-M8129) for monitoring communication status, such as data transmission, reception errors, and timeouts. It also provides specific instructions for reading from and writing to slave devices using FROM and TO commands, including handling broadcast messages and managing data lengths and addresses. This manual is written in Chinese.
| Communication Protocol | MODBUS-RTU |
|---|---|
| Data Length | 7 or 8 bits |
| Stop Bits | 1 or 2 |
| Max Data Length per Command | 64 registers |
| Max Data for RS Instruction | 140 |
| Slave Address Range | 1 to 255 |
The RS485 port supports switching between the Sanrong FEX programming port protocol and the MODBUS-RTU protocol.
The default communication timeout setting is 500ms (equivalent to 50 in the register setting).
Yes, you can send instructions to all slave stations by setting the slave address to 0.