This document covers the installation and operation of Detcon Model IR-700 IR700 combustible gas sensor and CO2 carbon dioxide gas sensor. It includes features such as sensor electronics design, modular mechanical design, and plug-in replaceable sensor.
The Detcon Model IR-700 is a non-intrusive 'Smart' sensor designed to detect combustible hydrocarbon gases in air within the 0-100% LEL range. It features Non-Dispersive Infrared (NDIR) optical technology, which uses an infrared lamp source and pyroelectric detectors to measure gas concentration by analyzing light absorption. Unlike catalytic bead sensors, this unit is resistant to poisoning from corrosive gases and can operate without oxygen.
| Detection Range (LEL) | 0-100% LEL |
|---|---|
| Detection Range (CO2) | 0-.3% to 0-100% by Volume |
| Electrical Outputs | 4-20mA and Modbus RS-485 |
| Electrical Classifications | Class I, Division 1, Groups B C D; Class I, Zone 1, Group IIB+H2 |
| Expected Service Life | 5 years or greater |
The sensor detects combustible hydrocarbon gases in air and CO2. It will not respond to non-hydrocarbons such as H2, NH3, CO, or H2S.
Typical zero calibration intervals are quarterly to semi-annual, and span intervals are semi-annual to annual.
Yes, unlike catalytic bead sensors, Detcon IR sensors can operate in the absence of an oxygen background.