Hui Dian Ke Ji HD250VXXA3TK Three-Phase Power Parameter Acquisition Module User Manual

The HD250VXXA3TK series of Hui dian ke ji is a three-phase power parameter acquisition module with features such as power supply voltage, AC voltage measurement error, AC current measurement error, and apparent power measurement error.


Hui Dian Ke Ji HD250VXXA3TK Three-Phase Power Parameter Acquisition Module User Manual - cover page
Brand
Hui dian ke ji
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
6
File format
PDF
File size
515 KB
Published
25 October, 2022
Updated
28 September, 2023
MD5 checksum
31A9B2ADE87680FAFC4859B801A9AA7E

About this manual

The Hui Dian Ke Ji HD250VXXA3TK is a three-phase power parameter acquisition module designed for measuring voltage, current, power, and frequency. It operates on a DC 8-28V power supply and features an isolated RS485 interface for communication. The device supports a frequency range of 45Hz to 55Hz and offers selectable low and high-speed data refresh rates.

The module utilizes the Modbus-RTU communication protocol to exchange data. It provides detailed register definitions for reading and writing various parameters, including device model, version, temperature, phase sequence, and specific measurements for A, B, and C phases such as current, voltage, apparent power, active power, reactive power, and power factor. Users can configure settings like baud rate, parity, and current/voltage transformer ratios via specific registers. This manual is written in Chinese.

What's inside

  • Product Specifications
  • Modbus-RTU Communication
  • Communication Precautions
  • Modbus Registers (Read/Write)
  • Phase A Parameters
  • Phase B Parameters
  • Phase C Parameters
  • Reserved Registers

Specifications

Power Supply VoltageDC 8-28V
Rated Power3W
Voltage Measurement ErrorTypical ±1% @50Hz
Current Measurement ErrorTypical ±1% @50Hz
Apparent Power Measurement ErrorTypical ±2% @50Hz
Active Power Measurement ErrorTypical ±4% @50Hz
Reactive Power Measurement ErrorTypical ±4% @50Hz
Voltage RangeAC 0-250V
Current RangeAC 0-50A
Frequency Range45Hz-55Hz
Operating Temperature-20°C to 50°C
Communication InterfaceIsolated RS485
Default Baud Rate9600
Max Nodes per Network32

Frequently asked questions

What is the default baud rate for the module?

The default baud rate is 9600 with N, 8, 1 settings.

How many nodes can be supported on the same network?

The module supports a maximum of 32 nodes on the same network.

What is the operating temperature range?

The module operates within a temperature range of -20°C to 50°C.