KLHA KM75B94 RS485 Ceiling Light Sensor User Manual

KM75B94 is a ceiling light sensor that uses the standard RS485 bus MODBUS-RTU protocol, allowing easy access to PLC, DCS, and other instruments or systems for monitoring illuminance state quantities. It features high reliability, excellent long-term stability, and customizable output methods.


KLHA KM75B94 RS485 Ceiling Light Sensor User Manual - cover page
Brand
KLHA
Category
Other Electronics
Document type
User Manual
Language
English
Pages
9
File format
PDF
File size
903 KB
Updated
28 September, 2023
MD5 checksum
D18F3F303AE93A99E6761AF4F1D90A29

About this manual

The KLHA KM75B94 is an RS485 ceiling light sensor designed for monitoring illuminance state quantities. It utilizes a high-precision sensing core to ensure reliability and long-term stability, supporting a measuring range of 0~65535Lux with a wavelength range of 380nm~730nm. The device operates on a DC6~24V power supply and supports a running temperature range of -40~80°C.

The manual provides instructions on how to wire the device and configure it using the standard RS485 MODBUS-RTU protocol. Users can read and modify device settings such as the device address, baud rate, and correction values. The document includes specific hexadecimal command examples for querying data, changing addresses, adjusting baud rates, and modifying correction values to ensure accurate readings.

What's inside

  • Technical Parameters
  • How to wiring
  • Application solution
  • Communication Protocol
  • Read Data
  • Read and modify device address
  • Read and Modify Baud Rate
  • Read Correction Value

Specifications

Illuminance measuring range0~65535Lux
Illuminance allow deviation±7%
Repeatability test±5%
Wavelength range380nm~730nm
Default baud rate9600 8 n 1
Power supplyDC6~24V 1A
Running temperature-40~80°C
Working humidity5%RH~90%RH

Frequently asked questions

What is the default device address?

The default device address is 1 when the device is shipped.

What is the default baud rate?

The default baud rate is 9600, 8, n, 1.

Can the device address be changed?

Yes, the device address can be changed using the Modbus-RTU protocol command 01 06 00 66 00 02 E8 14.