About this manual

The Starlight DK820 is an 8-channel rail-mounted relay switch controller for distributed intelligent lighting control systems. It provides 8 switching outputs at 20 A per channel, each with a manual switch, and supports LT-NET signals with 128 preset scenes and 128 zones.

This installation manual covers delivery checks, safety information, cable precautions, technical data, mounting on a 35 mm DIN rail, power and load connections, control signal wiring, and protection or recovery methods. The device is intended for installation by qualified professionals in distribution boxes. This manual is written in Chinese.

What's inside

  • Delivery and Unpacking
  • Safety Information
  • Operating Cable Precautions
  • Main Functions
  • Technical Data
  • Product Installation and Requirements
  • Detection, Protection, and Recovery Methods

Specifications

Switching outputs8 channels, 20 A per channel
Manual controlManual switch on each channel
Preset scenes128 scenes
Control zones128 zones
Operating temperature-5 °C to +45 °C
Supply voltage12 V DC
Protection classIP20
Dimensions144 × 90 × 66 mm (W × H × D)
MountingDIN35 rail mounting
Max load power≤ 4 kVA

Frequently asked questions

What is the supply voltage of the DK820?

The DK820 uses a 12 V supply and requires a 12 VDC power module.

How many DK820 modules can one 12 V 1 A power supply connect?

A 12 V 1 A power supply can connect to no more than 5 DK820 modules.

What is the maximum switching voltage of the DK820 relay?

The DK820 relay switch has a maximum cutting voltage of 277 V.

Can the relays be operated manually?

Yes, each channel is equipped with a manual switch for direct control.