MK Sentry Residual Current Devices (RCDs) Product Leaflet


MK Sentry Residual Current Devices (RCDs) Product Leaflet - cover page
Brand
Residual
Category
Other Electronics
Document type
Product Leaflet
Language
English
Pages
2
File format
PDF
File size
172 KB
Published
07 May, 2012
Updated
07 May, 2012
MD5 checksum
B38C44E30DC1E5C3C32F5B8EF6D71376

About this manual

The MK Sentry range of residual current devices (RCDs) includes double‑pole, four‑pole, pulsating DC, fault‑current‑sensitive and time‑delayed models with current ratings from 16 A to 100 A and tripping sensitivities from 10 mA to 300 mA. The devices are offered in two‑module and four‑module configurations for both AC and DC applications.

All devices comply with BS EN 61008:1995 and the 16th edition IEE Wiring Regulations, feature positive contact status indication, and incorporate a filtering device to protect against transient surges. Installation notes cover polarity, test‑button operation, and use as isolating switches when in the OFF position.

What's inside

  • Product range
  • Features
  • Dimensions
  • Technical specification
  • Electrical
  • Physical
  • Installation
  • Time Delayed RCDs
  • Testing

Specifications

Fault breaking capacity3 000 A (up to 10 000 A with BS 88 fuse)
Operating frequency50 Hz
Operating voltages2‑pole: 110 V / 230 V; 4‑pole: 230 V‑400 V
Ambient temperature (AC)-5 °C to +60 °C

Frequently asked questions

What standards do MK Sentry RCDs comply with?

All MK Sentry RCDs are designed to fully comply with BS EN 61008:1995 and the 16th edition IEE Wiring Regulations.

What is the maximum tripping time for a Sentry Time Delayed RCD?

The maximum tripping time of a Sentry Time Delayed RCD is 450 ms.

What fault breaking capacity do the RCDs provide?

The RCDs have a fault breaking capacity of 3 000 A, which can be increased to 10 000 A when backed up by a BS 88 fuse.