The new SpectrAlert® Advance selectable output speaker strobes and dual evacuation speakers can reduce ground faults and allow faster installation.


System Sensor SpectrAlert Advance Indoor Selectable Output Speaker Strobes Dual Voltage Evacuation Handbook - cover page
Brand
SYSTEM
Category
Other
Document type
User Manual
Language
English
Pages
4
File format
PDF
File size
904 KB
Published
05 April, 2012
Updated
30 September, 2023
MD5 checksum
5175C196AC39F84FB61D512932680BD9

About this manual

The SpectrAlert Advance series includes indoor selectable‑output speaker strobes and dual‑voltage evacuation speakers designed for fire‑protective signaling. The devices feature plug‑in mounting, field‑selectable candela settings, and automatic 12‑ or 24‑volt operation, reducing ground faults and speeding installation.

The handbook covers mounting procedures, wiring to the universal mounting plate, electrical compatibility with existing SpectrAlert products, and detailed specifications such as operating temperature, voltage options, and UL listings. It also includes ordering information, UL current‑draw data, and guidance for using the optional Sync‑Circuit™ module for zone synchronization.

What's inside

  • Features
  • Installation
  • Physical Specifications
  • Electrical Specifications
  • Synchronization Module
  • UL Current Draw Data
  • Ordering Information
  • Surface Mounting

Specifications

Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non‑condensing
Maximum Supervisory Voltage (speakers)50 VDC
Frequency Range400 Hz to 4000 Hz
Power Rating1 W or 2 W
Strobe Flash Rate1 Hz
Wall‑Mount Dimensions (SPS Speaker Strobe)6.0 in L × 5.0 in W × 47 in D

Frequently asked questions

How are the candela settings selected on the speaker strobes?

Candela settings are field‑selectable using a rotary switch, offering standard and high ranges such as 15, 30, 75, up to 185 candela.

What UL listings apply to the SpectrAlert Advance speaker strobes?

The speaker strobes are listed to UL 1480 and UL 1971 and are approved for fire‑protective signaling systems.

What is the operating temperature range for these devices?

They operate between 32 °F and 120 °F (0 °C to 49 °C).