WYQ-1 Controller User Manual

This document describes the features and characteristics of the WYQ-1 permanent magnet mechanism controller product from Chunxing Electric Power Technology, including remote control of opening/closing, manual control of opening/closing, monitoring and alarm of opening/closing circuit faults, voltage indication of energy storage capacitors, overcharging protection of energy storage capacitors, etc.


WYQ-1 Controller User Manual - cover page
Brand
春兴电力
Document type
User Manual
Language
Chinese
Pages
10
File format
PDF
File size
307 KB
Published
16 March, 2012
Updated
29 September, 2023
MD5 checksum
6EBEE1F3957889E5E125E655563F82AC

About this manual

The WYQ-1 permanent‑magnet controller is designed for single‑coil vacuum circuit breakers, providing remote and manual split/close functions, fault monitoring, and energy‑storage capacitor management. It consists of a control unit and external energy‑storage capacitors, mounted inside the breaker housing.

The manual covers product overview, mechanical dimensions, technical parameters, wiring diagrams, installation steps, operation procedures, troubleshooting, and ordering information, ensuring safe and reliable operation in power‑grid applications. This manual is written in Chinese.

What's inside

  • 概述
  • 產品結構
  • 產品主要技術參數
  • 產品原理及端子接線
  • 產品使用說明
  • 安裝運行與維護
  • 調試說明
  • 訂貨須知

Specifications

Rated supply voltage220 VAC
Rated supply frequency50 Hz
Command voltage (split/close)220 VDC
Split energy‑storage capacitor4700 µF / 250 V
Close energy‑storage capacitor30000 µF / 250 V
Charging voltage (split capacitor)95–105 V (default 100 V)
Minimum working voltage≥90 % of charging voltage
Charging power consumption≤300 VA
Regulation power consumption≤25 VA
AC contact break capacity30 VA (≤250 V, ≤2 A)
DC contact break capacity30 W (≤250 V, ≤2 A)
Insulation resistance≥100 MΩ
Dielectric strength2 kV (50 Hz AC)
Impulse voltage5 kV
Operating temperature range-10 °C to +55 °C
Extreme temperature range-25 °C to +70 °C
Maximum relative humidity90 % RH
Atmospheric pressure80–110 kPa

Frequently asked questions

What is the command voltage for split/close operations?

The controller uses a 220 VDC command voltage for both split and close signals.

What indicates a fault condition on the controller?

The fault indicator lamp lights and the fault relay contacts close, providing a fault output signal.

What is the adjustable charging voltage range for the split energy‑storage capacitor?

It can be set between 95 V and 105 V at the factory, with a default of 100 V.

Download PDF (307 KB)

More 春兴电力 Manuals