TCZX TCC-CK201 Switch Cabinet Intelligent Control Unit Manual

TCC-CK201 series switch cabinet intelligent control device has the functions of once simulation chart display, high voltage carrying display and locking output, intelligent language error prevention prompt, temperature and humidity control, RS485 communication function and so on.


TCZX TCC-CK201 Switch Cabinet Intelligent Control Unit Manual - cover page
Brand
TCZX
Category
Other
Document type
User Manual
Language
Chinese
Pages
7
File format
PDF
File size
234 KB
Published
13 March, 2012
Updated
30 September, 2023
MD5 checksum
1F75D5651048BE061F564DB2AE9B7126

About this manual

The TCC-CK201 series switch cabinet intelligent control unit provides functions such as breaker status indication, energy storage indication, grounding switch indication, position indication, intelligent voice prompts, high‑voltage display, cabinet lighting and RS485 communication. It is designed for 3‑35 kV indoor switch cabinets, including middle, hand‑car, fixed and ring‑network cabinets.

The document includes product overview, performance features, technical specifications, installation and wiring diagrams, typical design drawings and after‑sale service information. It also details sensor installation, temperature and humidity control, heating functions and communication capabilities. This manual is written in Chinese.

What's inside

  • Product Overview
  • Performance Features
  • Technical Specifications
  • Installation and Wiring Diagram
  • Typical Design Drawings
  • After‑sale Service
  • Communication Function

Specifications

Power supplyAC/DC 220 V ±10 % 50 Hz
Operating temperature range-20 °C to 70 °C
Maximum relative humidity95 % RH
Altitude ratingup to 3000 m
Temperature measurement range-20 °C to 99 °C
Temperature measurement accuracy±1 °C
Humidity measurement range60 % RH to 99 % RH
Humidity measurement accuracy±5 % RH
Insulation strength> 2000 V AC between enclosure and terminals
Insulation resistance> 100 MΩ between enclosure and terminals
LED voltage indicator rangeBus voltage ×0.15 ~ 0.65
Communication interfaceRS485

Frequently asked questions

What power supply does the TCC-CK201 unit require?

It operates from an AC or DC supply of 220 V with a tolerance of ±10 % at 50 Hz.

What communication protocol is provided for remote monitoring?

The device includes an RS485 communication interface for transmitting status information.

What are the temperature and humidity measurement ranges?

Temperature can be measured from –20 °C to 99 °C with ±1 °C accuracy, and humidity from 60 % RH to 99 % RH with ±5 % RH accuracy.

Download PDF (234 KB)