Xiao Ele JKB-R2Bd Combustible Gas Detector User Manual

JKB-R2Bd is a combustible gas detector and alarm that can be used to detect CH4, C3H8 and other combustible gases. The working principle is catalytic combustion. The detector converts the combustion gas concentration at the monitoring point into an electric voltage signal, then converts it into a digital signal, and transmits it to the controller via the bus. The controller calculates, analyzes, and displays the combustible gas concentration at the monitoring point and the working status of the detector. When the detector's sensor element is short-circuited or open-circuited, the detector can send a fault signal to the controller.


Xiao Ele JKB-R2Bd Combustible Gas Detector User Manual - cover page
Brand
JKB-R2Bd
Document type
User Manual
Language
Chinese
Pages
3
File format
PDF
File size
111 KB
Published
12 March, 2012
Updated
30 September, 2023
MD5 checksum
CCEE8233608E131906B34893BC2A9C09

About this manual

This manual describes the technical specifications and working principle of the JKB-R2Bd combustible gas detector, including detection gases, alarm settings, measurement range, response times, communication method, and environmental limits. It also outlines the explosion‑proof classification and physical dimensions of the device.

Installation, commissioning, and operation procedures are detailed, with wiring diagrams, calibration steps, storage recommendations, maintenance intervals, and common fault analysis. Warranty terms and service conditions are provided at the end of the document. This manual is written in Chinese.

What's inside

  • Technical Specifications
  • Working Principle
  • Wiring Diagram
  • Installation
  • Commissioning
  • Operation Instructions
  • Common Fault Analysis
  • Storage and Service Life
  • Precautions
  • Warranty Details

Specifications

Detection gasCombustible gas
Detection principleCatalytic combustion
CH4 alarm upper limit50% LEL
CH4 alarm lower limit25% LEL
C3H8 alarm upper limit50% LEL
C3H8 alarm lower limit2.5% LEL
Measurement range0–75% LEL
Response time<30 s
Recovery time<30 s
CommunicationRS‑485 bus
Operating temperature-40 °C to 70 °C
Humidity range0–95 % RH
Operating voltageDC 18 V–36 V
Dimensions187 mm × 107 mm × 65 mm
Weight850 g
Storage temperature-25 °C to 55 °C
Storage humidity<95 % RH
Sensor service life5 years

Frequently asked questions

What is the warranty period for the JKB‑R2Bd detector?

The manufacturer provides a one‑year free warranty for the detector.

How should the detector be stored when not in use?

Store it at temperatures between –25 °C and 55 °C with humidity below 95 % RH; if stored below 0 °C, bring it to room temperature for at least 2 hours before powering on.