Vaisala HMT100 Temperature Humidity Transmitter Manual

The Vaisala HMT100 temperature and humidity transmitter is designed for monitoring temperature and humidity in demanding environments, particularly in the HVAC field. It features full-range relative humidity measurement, fixed and remote probes, and the ability to display relative humidity, dew point, and temperature.


Vaisala HMT100 Temperature Humidity Transmitter Manual - cover page
Brand
HMT100
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
353 KB
Published
21 January, 2012
Updated
28 September, 2023
Model
HMT100
MD5 checksum
3E9D44F4B8196DCBE24E745691F0B12E

About this manual

The HMT100 transmitter is designed for demanding HVAC environments such as indoor spaces, livestock farms, greenhouses, indoor pools and outdoor installations. It uses Vaisala's HUMICAP® sensor technology for accurate relative‑humidity measurement and offers both wall‑mounted and remote‑probe configurations with optional display modes.

The manual details performance data, electrical connections (4‑20 mA or 0‑10 V outputs), power requirements, mechanical dimensions, enclosure protection (IP65/NEMA 4), and recommended calibration procedures using Vaisala handheld instruments or humidity calibrators. This manual is written in Chinese.

What's inside

  • Performance Overview
  • Installation Options
  • Technical Parameters
  • Electrical Input/Output
  • Calibration Procedure
  • Mechanical Parts and Materials
  • Environmental Conditions
  • Accessories and Options

Specifications

Relative humidity measurement range0 – 100 %RH
Relative humidity accuracy (0‑90 %RH)±1.7 %RH
Relative humidity accuracy (90‑100 %RH)±2.5 %RH
Temperature measurement range-40 – +80 °C
Temperature accuracy at +20 °C±0.2 °C
Current‑loop output4 – 20 mA (two‑wire)
Voltage output options0‑1 V, 0‑5 V, 0‑10 V
Power supply10 – 35 VDC / 24 VAC
Enclosure protection ratingIP65 (NEMA 4)
Sensor typeVaisala HUMICAP® 180

Frequently asked questions

Can the probe be replaced without recalibrating the transmitter?

Yes, the probe is interchangeable and does not require recalibration after replacement.