Fuyuan Lida FYXH-24.A Intelligent Central Signal Alarm User Manual

FYXH series intelligent central signal alarm device is an important part of the secondary part of the power plant and substation electrical system. It has the functions of strong function, high sensitivity, high reliability, low power consumption, signal memory and programming setting. It is an upgraded product of conventional signal alarm system.


Fuyuan Lida FYXH-24.A Intelligent Central Signal Alarm User Manual - cover page
Brand
FYXH-24.A
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
11
File format
PDF
File size
2.7 MB
Published
17 January, 2012
Updated
30 September, 2023
MD5 checksum
95CAE667E8CB2CCCB877ABA82366D9E6

About this manual

The FYXH-24.A is an intelligent central signal alarm designed for power plants, substations and industrial facilities. It supports 24 signal channels, offers flexible alarm sound options (electric whistle or bell), and features low power consumption with built‑in LED display and keypad for configuration.

The manual explains how to set channel parameters, use the recall function for fault history, perform self‑test, and install the unit. Detailed wiring diagrams, terminal tables, and dimension drawings are included, along with a warranty registration form. This manual is written in Chinese.

What's inside

  • Technical Introduction
  • Features
  • Technical Specifications
  • Physical Appearance
  • Function Usage
  • Parameter Settings
  • Memory Recall
  • Test Mode
  • Installation Dimensions
  • Wiring Diagram

Specifications

Input signal voltage rangeDC5V ~ DC250V
Power supply voltageAC/DC 220V ±20% or AC/DC 110V ±20%
Power consumption< 60W
Signal resolution10 ms
Operating temperature-10 °C ~ +50 °C
Number of channels (model FYXH-24.A)24
Internal DC supply5 V, 12 V
Alarm sound optionsElectric whistle or electric bell

Frequently asked questions

How do I set the alarm parameters for each channel?

After powering on, press the “Write” key three times to enter parameter setting mode, then use the cursor, +/‑ keys and Confirm to adjust channel settings.

How can I recall past fault events?

Press the “Recall” key; the display shows the first fault channel number, then press Confirm to step through subsequent fault channels until all are shown.

How do I enter the self‑test mode?

Press the “Mute” key three times; the unit enters self‑test, LEDs alternate and the whistle and bell sound alternately, then returns to normal after two cycles.