Beijiaan EXAO Series Analog Output Isolated Safety Barrier
This safety barrier converts analog signals from safe areas to isolated DC current or voltage signals for hazardous areas. It supports 1-in-1-out, 1-in-2-out, and 2-in-2-out configurations. The device is certified for use in hazardous zones 0-2 and IIA-IIC environments. It features electrical isolation, configurable input/output ranges, and DIN rail mounting. Key specs include 0.1% isolation accuracy, ≤2ms response time, and IP20 protection.
The product is designed for use with field actuators like valve positioners and electrical converters. It operates on 18–32VDC, weighs 130g, and is made of ABS plastic. Installation and usage must follow GB3836.15-2010 standards to ensure safety and compliance. This manual is written in Chinese.
Covers: Product Overview · Channel Configurations · Electrical Isolation · Certifications · Technical Specifications · Installation

BeijiaAn PFEXB-C4D1 Isolation Safety Barrier User Manual
The BeijiaAn PFEXB-C4D1 is a voltage output type isolation safety barrier designed to receive voltage signals from a safe area, process them through isolation and linearization, and output them to a control system or combined instrument in a hazardous area. It features three-terminal isolation (input, output, and power) and supports various input and output signal types, including 0-5V, 0-10V, and 4-20mA. The device is certified for Exia Ga hazardous areas and complies with GB 3836 explosion-proof standards. This manual is written in Chinese.
Covers: Main Technical Parameters · Application Wiring Diagram · Dimensional Structure · Installation Precautions · Power Supply Specifications · Performance Indicators
Latest BeijiaAn manuals
Beijiaan EXAO Series Analog Output Isolated Safety Barrier
Product Leaflet 2 pages · 419 KB · ZHBeijiaan EXAO series analog output isolated safety barrier for hazardous area signal conversion with Ex ia Ga IIC certification.
BeijiaAn PFEXB-C4D1 Isolation Safety Barrier User Manual
User Manual 2 pages · 510 KB · ZHThis manual covers the BeijiaAn PFEXB-C4D1 dual input dual output isolation safety barrier, including technical parameters, wiring diagrams, installation…
Which document do I need?
User Manual
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Questions answered in BeijiaAn manuals
What is the isolation accuracy?
The isolation accuracy is 0.1% of full scale.
From: Beijiaan EXAO Series Analog Output Isolated Safety Barrier
What is the maximum operating temperature?
The maximum operating temperature is +60°C.
From: Beijiaan EXAO Series Analog Output Isolated Safety Barrier
What is the explosion-proof rating of this safety barrier?
The PFEXB-C4D1 has an explosion-proof rating of Exia Ga for II C hazardous areas.
From: BeijiaAn PFEXB-C4D1 Isolation Safety Barrier User Manual
Can the input and output signals be customized?
Yes, the input signals can be 0-5V, 0-10V, or specified signals, and the output can be configured for specific ranges.
From: BeijiaAn PFEXB-C4D1 Isolation Safety Barrier User Manual