The NLON-01 adapter has downloadable applications for different drive types, with the default application in the adapter being for ACS600. If the application is not correct for the drive and the NLON-01 has been configured with a network management tool, the POW/ERR LED on the adapter will blink between red and green at a rate of 1 Hz. The appropriate application file to be loaded depends on the tool used. Most network management tools can download the application, but current versions of The Trane Company's Rover tool and Tridium's tool cannot. Like all DDCS fieldbus adapters, parameter 5005 must be set to DDCS (or Modus + DDCS) to enable communication between the adapter and the drive. When DDCS communication between the NLON-01 and ACH400 is working, parameter 51.01 should show 7. Parameters in group 51 are read-only values and manually changing them has no effect on the NLON-01.