The Mitsubishi FX1N Series Hardware Manual provides safety, installation, wiring and specification details for the FX1N programmable controllers.
About this manual
This hardware manual covers safety guidelines, recommended installation practices, and mounting options for the FX1N Series programmable controllers. It emphasizes the need for qualified personnel and outlines the required protective measures when working with the equipment.
The document also details power‑supply options, input and output specifications, wiring techniques, and environmental limits such as temperature, humidity and vibration resistance. Technical data and diagrams are provided to aid proper configuration and maintenance of the controllers.
What's inside
- Safety Guidelines
- Installation Notes
- Mounting Arrangements
- Power Supply
- Inputs
- Outputs
- Diagnostics
- General Specifications
- Wiring
- Appendix
Specifications
| Operating Temperature | 0 to 55 °C (32 to 131 °F) |
|---|
| Storage Temperature | -20 to 70 °C (-4 to 158 °F) |
|---|
| Operating Humidity | 35 to 85% RH, no condensation |
|---|
| Noise Immunity | 1000 Vp‑p, 1 µs, 30‑100 Hz |
|---|
| Dielectric Withstand Voltage | 1500 V AC > 1 min. |
|---|
| Insulation Resistance | 5 MΩ @ 500 V DC |
|---|
| Grounding Class | Class D (≤100 Ω) |
|---|
| Certification | UL/cUL, EC Directive EMC & LVD |
Frequently asked questions
What safety precautions are required when installing the FX1N controller?
Installation must be performed by trained engineers or service personnel who follow local and national safety standards, and the controller should be mounted in a conductive shielded control box.
What power‑supply options are available for the FX1N Series?
The FX1N can be powered from an AC supply, a 24 V DC supply, or a 12 V DC supply, each with specific wiring guidelines.
What are the environmental limits for operating temperature?
The controller operates between 0 °C and 55 °C and can be stored from –20 °C to 70 °C.
How should the controller be mounted to meet vibration requirements?
For DIN‑rail mounting, vibration resistance is 0.035 mm half‑amplitude at 57 Hz; for direct mounting, 0.075 mm half‑amplitude at 57 Hz.